High voltage power transformer bushings (230 kV and above) are a known seismic vulnerability, often failing during significant earthquakes and causing potential disruption to the power supply. This occurs most commonly when the dynamic resonance between the transformer tank and the mounted bushing causes excessive amplification of the seismic demands to the bushing, leading to failure. This study evaluates multiple existing transformer designs that include stiffness discontinuities near the foundation, and the impact on the system dynamic response that results from mitigating these discontinuities with simple and potentially retrofittable blocking below the tank corners. The results of the study show that modifying the transformer bases to have an increased stiffness between the foundation and transformer tank causes a reduction in seismic high voltage bushing stress—with an average reduction of 37%.

Original languageEnglish
Pages (from-to)2396-2408
Number of pages13
JournalEarthquake Engineering and Structural Dynamics
Volume55
Issue number10
Early online dateMay 12 2026
DOIs
StateE-pub ahead of print - May 12 2026

Keywords

  • dynamic response
  • power transformers
  • seismic performance
  • structural design
  • transformer bushings

INL Publication Number

  • INL/JOU-25-84266
  • 198227

Fingerprint

Dive into the research topics of 'The Impact of High Voltage Power Transformer Base Design on Bushing Seismic Amplification'. Together they form a unique fingerprint.

Cite this