Safety Related Concerns with Installation and Use of Switch-Rated Plug/Receptacle Combinations in Lieu of Metal-Enclosed Disconnect Switches

  • John J Whipple
  • , Richard T Waters

Research output: Contribution to conferencePaperpeer-review

Abstract

The manufacturers of Nationally Recognized Testing Laboratory (NRTL) listed, switch-rated, plug and receptacle combinations tout their convenience, reliability, efficiency, and compliance with both the National Fire Protection Association (NFPA) 70®, National Electric Code (NEC), and National Fire Protection Association 70E®, The Standard for Electrical Safety in the Workplace, as advantages to using these products in lieu of traditional metal-enclosed disconnect switches. The purpose of this paper is to raise awareness of several unintended consequences that can result when replacement involves high energy cord and plug connected equipment. This paper describes several possible issues in complying with the NFPA 70 Articles 110 and 400 and NFPA 70E Articles 110 and 130 that should be considered when using load rated plug/receptacle combinations. This paper is intended to address high energy circuits typically associated with 480 volt pin and sleeve type connections in applications where incident energy levels may exceed 1.2 calories/centimeter² (cal/cm²).
Original languageEnglish
StatePublished - Mar 1 2023
EventIEEE Electrical Safety Workshop - Reno, United States
Duration: Mar 14 2023Mar 17 2023

Conference

ConferenceIEEE Electrical Safety Workshop
Abbreviated titleESW 2023
Country/TerritoryUnited States
CityReno
Period03/14/2303/17/23

INL Publication Number

  • INL/CON-22-70488
  • 145640

Fingerprint

Dive into the research topics of 'Safety Related Concerns with Installation and Use of Switch-Rated Plug/Receptacle Combinations in Lieu of Metal-Enclosed Disconnect Switches'. Together they form a unique fingerprint.

Cite this