TY - GEN
T1 - Investigation of a dynamic power line rating concept for improved wind energy integration over complex terrain
AU - Phillips, Tyler B.
AU - Senocak, Inanc
AU - Gentle, Jake P.
AU - Myers, Kurt S.
AU - Anderson, Phil
N1 - Publisher Copyright:
Copyright © 2014 by ASME.
PY - 2014
Y1 - 2014
N2 - Dynamic Line Rating (DLR) is a smart grid technology that allows the rating of power line conductor to be based on its realtime temperature. Currently, conductors are generally given a conservative static rating based on near worst case weather conditions. Using historical weather data collected over a test bed area in Idaho, we demonstrate there is often additional transmission capacity not being utilized under the current static rating practice. We investigate a DLR method that employs computational fluid dynamics (CFD) to determine wind conditions along transmission lines in dense intervals. Simulated wind conditions are then used to calculate real-time conductor temperature under changing weather conditions. In calculating the conductor temperature and then inferring the ampacity, we use both a steady-state and transient calculation procedure. Under low wind conditions, the steady-state assumption predicts higher conductor temperatures which could lead to unnecessary curtailments, whereas the transient calculations produce temperatures that can be significantly lower, implying the availability of additional transmission capacity. Equally important, we demonstrate that capturing the wind direction variability in the simulations is critical in estimating conductor temperatures accurately.
AB - Dynamic Line Rating (DLR) is a smart grid technology that allows the rating of power line conductor to be based on its realtime temperature. Currently, conductors are generally given a conservative static rating based on near worst case weather conditions. Using historical weather data collected over a test bed area in Idaho, we demonstrate there is often additional transmission capacity not being utilized under the current static rating practice. We investigate a DLR method that employs computational fluid dynamics (CFD) to determine wind conditions along transmission lines in dense intervals. Simulated wind conditions are then used to calculate real-time conductor temperature under changing weather conditions. In calculating the conductor temperature and then inferring the ampacity, we use both a steady-state and transient calculation procedure. Under low wind conditions, the steady-state assumption predicts higher conductor temperatures which could lead to unnecessary curtailments, whereas the transient calculations produce temperatures that can be significantly lower, implying the availability of additional transmission capacity. Equally important, we demonstrate that capturing the wind direction variability in the simulations is critical in estimating conductor temperatures accurately.
UR - https://www.scopus.com/pages/publications/84919933789
U2 - 10.1115/FEDSM2014-21377
DO - 10.1115/FEDSM2014-21377
M3 - Conference contribution
AN - SCOPUS:84919933789
T3 - American Society of Mechanical Engineers, Fluids Engineering Division (Publication) FEDSM
BT - Symposia
PB - American Society of Mechanical Engineers (ASME)
T2 - ASME 2014 4th Joint US-European Fluids Engineering Division Summer Meeting, FEDSM 2014, Collocated with the ASME 2014 12th International Conference on Nanochannels, Microchannels, and Minichannels
Y2 - 3 August 2014 through 7 August 2014
ER -