Skip to main navigation Skip to search Skip to main content

A RELAP5-3D/LSTM model for the analysis of drywell cooling fan failure

Research output: Contribution to journalArticlepeer-review

18 Scopus citations

Abstract

A RELAP5-3D/LSTM model was created to analyze the failures of two drywell cooling fans at a nuclear power plant. A total of four fan coil units (FCUs) each comprised of a water-cooled heat exchanger and a centrifugal fan located in the drywell provide cooling via a closed nitrogen loop to the primary containment of the boiling water reactor. A Reactor Excursion and Leak Analysis Program (RELAP5-3D) thermal hydraulic model was created to simulate the steady-state normal operation of the FCUs. Historical data from the plant Process Information (PI) system was synchronized in time for a total of 33 Plant Management Information System (PMIS) tags per FCU representing: (1) the temperatures at various locations within the drywell, (2) inlet, outlet, and dewpoint temperatures at the FCUs, (3) reactor power, and (4) water coolant flowrate and temperature. Because the inlet temperature sensor for the two fans that failed did not provide consistent data prior to the failures, a long short-term memory (LSTM) recurrent neural network was trained to predict the FCU inlet temperature history based upon the states of the other valid PMIS points. RELAP5-3D simulations were performed using the measured FCU inlet temperatures, as well as the LSTM-generated temperatures, and the resulting FCU outlet temperatures were compared. The simulation results using the measured and predicted FCU inlet temperature were shown to be within 7.35% and 5.16%, respectively, of the values reported by the PI system. Thus, a viable approach has been demonstrated to predict the expected FCU outlet temperature. By comparing real-time measurements of FCU outlet temperature with predictions such as those presented here, off-normal operation can be readily detected. The use of RELAP5-3D with the LSTM results was successfully implemented to prototype a physics-based anomaly detection model for the drywell FCUs.

Original languageEnglish
Article number103540
JournalProgress in Nuclear Energy
Volume130
DOIs
StatePublished - Dec 2020

Keywords

  • Anomaly detection
  • Drywell cooling fan
  • Fan coil unit
  • Long short-term memory
  • Machine learning
  • Process information
  • RELAP5-3D
  • Thermal hydraulics

Fingerprint

Dive into the research topics of 'A RELAP5-3D/LSTM model for the analysis of drywell cooling fan failure'. Together they form a unique fingerprint.

Cite this